General X-Ray
Specifications
Section 13090, X-Ray Protection
[See the five other
Specifications Pages by using links above & below]
[Also see the Lead Sheet Stock Thickness, Weights & Sizes page]
PART 1 -
GENERAL
1.01 SUMMARY
A. This section includes: The requirements for furnishing and installing X-Ray Protection Materials including lead backed gypsum wallboard, lead lined doors, lead lining of door frames, window frames and x-ray protective lead glass.
1.02 RELATED
DOCUMENTS
A. The requirements of the General Conditions, Supplementary Conditions, and Division 1, General Requirements apply to the work of this Section.
B. Section 09 2960-Lead Backed Drywall, Section 08 8860–X-Ray Lead Glass, Section 08 1420–Flush Wood doors, Section 08 1426–Plastic Faced Flush Wood doors, as applicable.
1.03 QUALITY ASSURANCE
A. Standards: Comply with requirements of National Council on Radiation Protection and Measurement (NCRP) Report No. 49 & 147 "Structural Shielding and Design Evaluation for Medical Use of X-rays and Gamma Rays of Energies up to 10MeV"
1. Comply with requirements of local, regulatory agencies where standards or criteria exceed NCRP Report Numbers 49 and 147.
B. Acceptable Manufacturer: Ray-Bar Engineering Corporation, Toll Free (800) 567-XRAY (9729) Phone:(626) 969-1818 · Fax 626) 969- 6510 · www.raybar.com, e-mail: sales@ray-bar.com / (no known equal). A recognized manufacturer regularly engaged in the production of the products as specified herein.
C. Fabricator-Installer Qualifications: Fabricator-Installer shall be experienced in and equipped for work of fabrication and installation equal to standards specified. The contractor shall furnish evidence of Fabricator- Installer having not less than ten (10) years experience in successful fabrication-installation of radiation protection similar to work specified herein utilizing properly trained personnel with good hygiene practices and proper lead handling training and procedures.
1. Fabricator-Installer shall furnish proof of insurance certifying Fabricator-Installer is specifically insured in the fabrication and installation of X-ray Protection Materials for Shielding.
1.04 SUBMITTALS
A. Product Data: Submit manufacturers printed data and specifications for each item of radiation shielding and accessories proposed for use and indicate compliance with applicable safety codes.
B. Shop Drawings: Submit shop drawings indicating thickness of lead, in compliance with Radiation Shielding Report, details of construction products and all other details to clearly define method of installation to assure that the required lead shielding protection will be obtained.
C. Certification: Submit at completion of work, certificate of compliance from manufacturer and Fabricator-Installer stating that all material has been produced and installed in accordance with this specification.
1.05 DELIVERY, STORAGE AND HANDLING
A. Leadlined Door and Window Frames: Comply with requirements of Section 08 1420-Steel Doors and Frames.
B. Leadlined Wood Doors: Comply with requirements of Section 08 1400 -Flush Wood Doors or Section 08 1426 -Plastic Faced Flush Wood Doors, as applicable.
Specifically 08 3440 – Radiation Protection Doors
Product Handling: Keep flat until ready to use. NEVER store outdoors, Never store in sun or near moisture.
C. Lead Backed Gypsum Wallboard: Comply with requirements of Section 09 2900- Gypsum Board.
Specifically 09 2960 – Lead Backed Drywall
Product Handling: Keep flat until ready to use. NEVER store outdoors, Never store in sun or near moisture.
D. X-Ray Lead Glass: Comply with requirements of Section 08 8000 – Glazing.
Specifically 08 8860 – X-Ray Lead Glass
Product Handling: Follow Manufacturer / Fabricator specific handling and storage requirements to prevent damage, scratches or breakage of fragile X-Ray Lead Glass. NEVER store outdoors, set flat or use knives or strong cleaners on X-Ray Lead Glass.
PART 2 -
PRODUCTS
2.01 APPROVED MANUFACTURERS
A. Ray-Bar Engineering Corporation, 697 W Foothill Blvd, Toll Free (800) 567-XRAY (9729) Phone:(626) 969-1818 · Fax (626) 969- 6510 · www.raybar.com, e-mail sales@raybar.com/ (no known equal). A recognized manufacturer regularly engaged in the production of X-Ray Protection Materials (no known equal).
2.02 MATERIALS
AND FABRICATION
A. Lead Sheet: In compliance with Federal Specification QQ-L-201f, Grade C, 99.9% pure, and ASTM B 749, Type L5 1121. Thickness as indicated on Lead Protection Schedule, to 7’0” high, minimum national standard on walls (unless otherwise noted).
B. Lead Backed Gypsum Board: As manufactured by Ray-Bar Engineering Corporation; ASTM C 36, and as follows:
C. Fire rated lead backed 5/8” gypsum board (type RB-LBG) to be utilized at any fire rated lead lined partitions (such as partition design U430) and identified with proper yellow U.L Label laminated on actual lead side indicating shielding material manufacturer and current fire resistance listing and U.L. classification per the current U.L. certification directory and as tested in accordance with the standard fire test of building construction and materials per ANSI / UL263 (ASTM E119, NFPA 251). There are absolutely no substitutions allowed.
D. Lead Lined Wood Doors: Comply with applicable requirements of Section 08 1420, "Flush Wood Doors" and Section 08 1426, "Plastic Faced Flush Wood Doors", as applicable.
E. Leadlined Hollow Metal Door Frames: Comply with requirements of Section 08 1420-Steel Doors and Frames.
F. View Window Frames: Ray-Bar lead lined Telescopic Steel View Window Frame, fabricated from 16 gauge jetcoat electro-Galvanized Steel lead lined with equal or greater lead as in wall that window occurs in and telescope to wall thickness required.
G.Lead Glass: As specified in Section 08 8000, "Glass and Glazing". X-Ray Protective type, (Ray-Bar X-Ray Lead Glass) Federal Specification DD-G-451, in single or multiple layers of x-ray lead glass with lead equivalent not less than that of system in which it is installed. Glass must be clearly labeled or identified as “X-Ray Lead Glass”. X-Ray Safety Glass permanently labeled as impact resistant and must be utilized in any door vision lites or windows that occur within 24” of any door opening and must be permanently labeled in compliance with ANSI Z97.1 and CPSC 16 CFR Part 1201, CAT II for impact resistance, such as Ray-Bar X-Ray Safety Glass, manufactured solely by Ray-Bar Engineering Corporation, email: sales@raybar.com · www.raybar.com (no known equal)
H. Floor Lead: If required or indicated on Lead Protection Schedule, a single layer of unpierced lead sheet meeting Federal Specification QQ-L-201f, Grade C, 99.9% pure and of the thickness specified on Lead Protection Schedule
I. Ceiling Lead Shielding: Lead backed 5/8” drywall to be installed on ceiling areas when required to provide shielding for occupancy above on areas where appropriate and indicated on plans per shielding report provided by physicist of record for project. All penetrations and joints between lead backed drywall sheets are to be properly shielded with same techniques as on wall partitions.
a) Ceiling must be framed for “hard lid” at 12” on center for support and to prevent sagging.
b) Framing to be of size and gauge of metal as determined and specified by the project structural engineer.
c) T-Bar, grids and suspended ceilings are not acceptable systems for proper radiation shielding.
d) All penetrations in leadlined ceilings such as HVAC, fire sprinklers, ducts, etc. must be properly backed with lead of same thickness as in ceiling with proper overlaps. Lead Lined access panels to be installed where required to provide continuous radiation protection
PART 3 -
EXECUTION
3.01 INSTALLATION
A. Lead Backed Gypsum Wallboard:
B. Leadlined Doors: Refer to Section 08211, "Flush Wood Doors” and Section 08212, "Plastic Faced Flush Wood Doors" as applicable, for installation requirements.
1. Finish hardware is specified in Section 08710, "Finish Hardware". Locksets are to be leadlined.
C. Built-In Items: Where other built-in items penetrate lead lining, provide lead shield of same thickness as in surrounding wall partition as required to maintain continuity of shielding system. Install in strict accordance with manufacturer’s instructions and recommendations.
D. Where outlet boxes, junction boxes, ducts, conduit and similar items prevent the use of shields, provide lead sleeves or lead lining or backing as required with proper overlaps.3.03 CERTIFICATION1. Provide lead lining, sleeves, shields and other protections of equivalent thickness of lead as used in the wall partition shielding system that each penetration occurs in.
2. Properly clean up and disposal or recycle all sheet lead trimmings and debris. Never dispose of lead materials in general trash or refuse.
RAY-BAR ENGINEERING CORPORATION |
Toll
Free: 1(800) 567-XRAY (9729) Telephone: (626) 969-1818 Fax: (626) 969-6510 |